HOW OFTEN DOES FIRE ALARM CABLE NEED TO BE SUPPORTED?

Content
follow us
Oct 19, 2022

The answer to this question is not as straight forward as one may think. Fire alarm cables (Power-Limited) can be installed exposed (not in raceway) as long as it is protected against physical damage.

On most installations, a basic rule of thumb to use is that any fire alarm cable installed above 7 feet can be installed exposed; below 7 feet the cables shall be in a raceway.

The National Electrical Code requires that fire alarm cables passing through a floor be sleeved in a raceway up to a height of 7 feet, as described above. This is to offer protection from physical damage to the cable itself. Below we have a picture of an installation at a new office building.

When fire alarm cables enter or exit a raceway that is being used to provide protection against physical damage, NEC 300.15(C) requires that a fitting be used on the ends of the conduit in order to protect the cables from abrasion.